Ask Shorty

Parallel circuit

Receptacles on one circuit give each load its own path from the black wire to the white. You switch loads on and off and watch their amps add up on the wire from the breaker.

Open the visualFree, no sign-up. Works on a phone, tablet, computer, or projector.
Three receptacles on one cable, each feeding its own load

What to try

  1. 1Start with the lamp and the space heater on. The feed wire carries 13.0 amps. That is 0.5 for the lamp plus 12.5 for the heater.
  2. 2Set Space heater to Off. The lamp still gets 120 volts, because it has its own path.
  3. 3Turn the space heater back on and set Iron to On. The feed wire now carries 23.0 amps, more than the 20 amp breaker is made for.

NEC 2026 sections it covers

240.4(D)
12 AWG copper gets a 20 A breaker at most.
Table 210.21(B)(3)
A 20 A circuit with several receptacles may use 20 A receptacles.
210.12(B)
Bedroom circuits in a home also need AFCI protection.

Section numbers only. Read the full text in your code book. Temperatures and times in the visual are teaching models.